| Rated power (kVA for pf = 0.8) |
160 |
200 |
250 |
300 |
400 |
500 |
600 |
800 |
| Active power (kW) |
160 |
200 |
250 |
300 |
400 |
500 |
600 |
800 |
| Normal AC input |
| Rated voltage |
380 V - 10% to 415 V + 15% - three-phase (1) |
| Frequency |
50 or 60 Hz +/- 5% |
| Current distortion |
THDI < 4% with THM filter |
| Power factor |
Up to 0.95 with THM filter |
| Bypass AC input |
| Voltage |
380 V, 400 V or 415 Veff +/- 10% - three-phase + neutral (1) |
| Frequency |
50 or 60 Hz +/- 5% |
| Output |
| Phase-to-phase voltages |
380 V, 400 V or 415 Veff +/- 1% - three-phase + neutral (1) |
| Frequency |
50 or 60 Hz +/- 0.25% |
| Permissible overload |
150% In for 1 minute, 125% In for 10 minutes |
| Voltage distortion (THDU) (3) |
<2% ph/ph, <5%ph/N for linear loads <3% ph/ph, <5% ph/N for non-linear loads |
| Short circuit capacity |
2.33 In-1 s (2) |
| Transient voltage variations |
+/- 5% for 0% to 100% or 100% to 0% step load |
| Battery characteristics |
| Backup Time |
8, 10, 15, 20, 30, 60 minutes |
| Type |
sealed lead-acid (5 or 10 years life) |
| Input/output efficiency |
| At 100% load |
up to 94.5% |
| At 50% load |
up to 95% |
| Environment |
| Heat losses (3) in kW |
8.8 |
12.4 |
13.5 |
16.7 |
23 |
24.2 |
34.5 |
37.3 |
| Storage temperature range |
-25C to +45C (with batteries) |
| Operating temperature range |
0C to 35C (40C for eight hours) |
| Noise level (dBA) |
<68 |
<68 |
<69 |
<69 |
<72 |
<72 |
<72 |
<75 |
| Standards |
| Construction and safety |
IEC 62040-1, IEC 60950, IEC 50091-1 |
| Performance and topology |
IEC 62040-3, EN 50091-3 |
| Design and Manufacture |
ISO 14001, ISO 9001, IEC 60146 |
| EMC |
IEC 62040-2 and EN 50091-2 level B |
| Certifications and marking |
TUV, CE |
(1) Other voltages on request: 208, 220, 480 V (2) 2.33 = 1.67 2 (operation in current-limiting mode for a peak value of 1.67 In). In = rated output current (for pf = 0.8) (3) The loses indicated are for the cabinets operating at full rated load with the battery float charging. |